1. Scope
This specification is for code designations and properties of insulations for loose-fill applications.
2. References
Reference is made in this specification to the following documents. The latest issues, amendments, and
supplements to these documents shall apply unless otherwise indicated.
SABIC Engineering Standards (SES)
N01-F10 Corrosion Protection of Insulated Materials
S22-G01 Management and Control of Non-Asbestos Respirable Fibres (NARFs)
American Society for Testing of Materials (ASTM)
E 84 Standard Test Method for Surface Burning Characteristics of Building Materials

  1. Materials
CODE
405(1) 406(1) 407
Material Designation Slag wool, loose Slag wool, granulated Expanded silica (perlite)
Recommended Temperature Range -95  C to 650  C (-140  F to +1,200  F) -95  C to 650  C (-140  F to +1,200  F) Untreated:38  C to 870  C

(+100  F to 1,600  F)

Silicone treated: 260  C (500  F) max

Purpose Insulation for spaces not easily accessible Insulation for spaces not easily accessible Insulation for spaces not easily accessible
Material Description Loose spun slag wool Granulated or pelleted spun slag wool Expanded silica. Specify grade:

PI 40 (a) PI 65 (b)

Maximum Leachable Chlorides, see SES N01-F10 Below 100 ppm Below 100 ppm Below 100 ppm
K Factor W/cm2/cm. C [Btu/(h)(ft2)(  F/in)] 4.5 x 10-4 at 93  C mean (0.31 at 200  F) 6.2 x 10-4 at 204  C mean (0.43 at 400  F) 8.2 x 10-4 at 316  C mean (0.57 at 600  F) 4.5 x 10-4 at 93  C mean (0.31 at 200  F) 6.2 x 10-4 at 204  C mean (0.43 at 400  F) 8.2 x 10-4 at 316  C mean (0.57 at 600  F) (a) 3.0 x 10-4 at 46  C mean (0.21 at 115  F) (b) 3.6 x 10-4 at 46  C mean (0.25 at 115  F)
Moisture Resistance or Water Vapor Permeability Poor Poor Poor
Density kg/m3 (lb/ft3) Min 80 (5) Shipping density 128 (8) 80 (5) (a) 64 (4) (b) 104 (6.5)
Flame-Spread/Smoke-Density Rating, see ASTM E 84 25/50 or less 25/50 25/50 or less 25/50 25/50 or less 25/50
Notes Void into which these loose fill materials are poured shall be adequately sealed to prevent moisture absorption;

water-repellent; nonsettling; resilient; noncorrosive; and oil coated to reduce dusting. See SES N01-F10 for metal substrate protection required.

Void into which these loose fill materials are poured shall be adequately sealed to prevent moisture absorption;

water-repellent; nonsettling; resilient; and noncorrosive. See

SES N01-F10 for metal substrate protection required.

Water absorbent. Void into which these loose fill materials are poured shall be adequately sealed to prevent moisture absorption; and water-repellent.

Silicone-treated expanded silica is available at a higher cost. See SES N01-F10 for metal substrate protection required.

Respirable fiber. See SES S22-G01.