1. SCOPE
…………..
2. REFERENCES
3. MATERIALS

1. Scope
This specification covers coatings and coverages for insulation.
2. References
Reference is made in this specification to the following documents. The latest issues, amendments, and
supplements to these documents shall apply unless otherwise indicated.
SABIC Engineering Standards (SES)
N01-F10 Corrosion protection of insulated equipment
American Society for Testing of Materials (ASTM)
ASTM B209 specification for Aluminum and the Aluminum-Alloy sheet and plate
ASTM E84 Surface burning characteristics of building materials.
3. Materials
CODE 709 (Fibrated asphalt cutback)

Material Designation Fibrated asphalt cutback
Recommended Temperature

Range

-51 to +163  C (-60 to +325  F) unless indicated otherwise
Purpose A weather- and chemical-resistant vapor-barrier mastic finish for thermal insulation
Material Description Mastic consisting of an asphalt-solvent cutback vehicle, fibers, and fillers of spraying or hard application consistency as specified on purchase order
Maximum Leachable Chlorides, see

SES N01-F10

Below 250 ppm
Moisture Resistance or Water

Vapor Permeability

Very low water vapor permeability
Flame-Spread/Smoke-Density

Rating, See ASTM E 84

Greater than 25/50. Do not use indoors without sprinkler protection or a fireproof finish.
Note Does not resist solvents and oils. Also used as a joint sealer and bedding compound. Contains volatile solvent and should not be allowed to contact hot surfaces during application. See SES N01-F10 for metal substrate protection required.

CODE 710 (Glass cloth – open weave)

Material Designation Glass cloth – open weave
Recommended Temperature +204  C (+400  F)
Range
Purpose Reinforcement in mastic for thermal insulation
Material Description Open-weave glass cloth produced from glass fiber yarns and compatible with accepted waterproofing and coating compounds. Leno weave to provide fixed thread spacing. Waterproof colorless weave set treatment to minimize distortion of thread spacing.
Maximum Leachable Chlorides, see Below 100 ppm
SES N01-F10
Dimensions See manufacturer’s literature
Flame-Spread/Smoke-Density 25/50 or less
Rating, See ASTM E 84
Specifications, Qualifications, Thread count 10 x 10/in2 min, 12 x 13/in2 max. Weight 10 lb/100 yd2 min. Tensile strength by strip method 50 lb/in min in warp direction, and 30 lb/in min in fill direction. Samples to be conditioned and tested at 65% relative humidity. See SN100P for metal substrate protection required.
Limitations
Approved Materials and Vendors Glass Cloth, Style 1659/Geon

J. P. Stevens and Co., Inc.

Glass Cloth, PGM 207 10 x 10

Perma Glas-Mesh Corp.

Woven Glass Scrim Fabric, Resin Treated Style 1659

Burlington Industries, Inc.

Luben Scrim Fabric Style No. 59(a)

Alpha Associates, Inc.

Fiber Glass Serium Style No. 1659

Clark Schwebel Fiber Glass Corp.

No. 10 Chil-Glas

Childers Products Co.

CODE 714 (Poultry netting)

Material Designation Poultry netting
Purpose Reinforcement in finishes for thermal insulation
Material Description Iron or steel wire mesh, galvanized 1 in size
Dimensions See manufacturer’s literature
Specifications, Qualifications, Limitations Iron or steel wire, 20 gage, woven and galvanized. Mesh size 1 in nominal hexagonal openings.
Approved Materials and Vendors Poultry Netting

Most mill supply houses, insulation distributors, and applicators

DE 714.1 (Poultry netting, coated)

 

Material Designation Poultry netting, coated
Purpose Reinforcement in finishes for thermal insulation
Material Description Galvanized iron or steel wire woven and vinyl coated after weaving, 1 in size
Maximum Leachable Chlorides, see

SES N01-F10

Below 40,000 ppm
Dimensions See manufacturer’s literature
Note Preferred for use with emulsion coatings such as Code 734 and in corrosive atmospheres. Galvanized iron and steel wire woven and vinyl-coated poultry netting. Mesh size 1 in nominal hexagonal openings. See SES

N01-F10 for metal substrate protection required.

Approved Materials and Vendors Vinyl-Coated Poultry Wire

Most mill supply houses, insulation distributors, and applicators

CODE 716 (Smooth aluminum jacket, 0.4 mm (16 mil)

 

Material Designation Smooth aluminum jacket, 16 mil
Purpose A finish for thermal insulation where weather resistance, cleanliness, appearance, oil or solvent spills, or fumes are factors
Material Description Smooth aluminum in roll form with a protective backing on inner surface
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: 914 mm or 1220 mm (36 or 48 in) Length: Rolls of 30 m(100 ft) minimum

Thickness of aluminum:0.4 mm (0.016 in) nominal

Note Attacked by most acids, chlorides, and some hydroxides. Check exposure before specifying. The protective backing shall be a minimum of 65 mµ (2.5 mil) total thickness coextruded polyethylene and DuPont Surlyn continuously heat-sealed to the metal. The Surlyn shall be a minimum of

25 mµ (1 mil). The protective backing shall qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.

Approved Materials and Vendors Aluminum Jacket with 2.5 Mil Poly/Surlyn

Childers Products Co.

Sure-Fit Roll Jacketing with 2.5 Mil Poly/Surlyn

Pabco Division of Fibreboard Corp.

16 Mil Aluminum Jacket with 2.5 Mil Poly/Surlyn

RPR Products, Inc.

 

CODE 716.5 (Smooth aluminum jacket, (16 mil) acrylic-coated)

 

Material Designation Smooth aluminum jacket, (16 mil) acrylic-coated
Purpose A finish for thermal insulation where weather or chemical resistance, cleanliness, appearance, oil or solvent spills, or fumes are factors
Material Description Smooth aluminum in roll form with a white acrylic coating on exterior and a protective backing on inner surface
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: Standard 36 in (48 in at additional cost) Length: Roll of 100 ft/min

Thickness of aluminum: 0.016 in nominal

Note Exterior surface to have a white acrylic coating nominal 0.8 mil dry-film thickness. Some acids will attack coating. Check exposure before specifying. The protective backing shall be a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The

protective backing must qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.

Approved Materials and Vendors Aluminum Jacket, Acrylic Finish with 2.5 Mil Poly/Surlyn

Childers Products Co.

Acrylic Coated Aluminum Jacket with 2.5 Mil Poly/Surlyn

RPR Products, Inc.

Sure-Fit Roll Jacketing, Acrylic Coated with 2.5 Mil Poly/Surlyn

Pabco Div. of Fibreboard Corp.

 

CODE 716.6 (Deep-corrugated aluminum jacket, 16 mil)

 

Material Designation Deep-corrugated aluminum jacket, 16 mil
Purpose A finish for thermal insulation on vertical vessels. Preferred finish where rigidity, weather resistance, cleanliness, appearance, oil or solvent spills, or fumes are factors.
Material Description Aluminum sheets with 11/4 in corrugations and a protective backing on the interior surface. A more rigid material than Code 716. Finish: smooth or cross-crimped as specified on order.
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: 33 in (36 in available at added cost) Length: Up to 12 ft

Thickness: 0.016 in nominal

Note Attacked by most acids, chlorides, and some hydroxides. Check exposure before specifying. The protective backing shall be 40 lb/3000 ft2 kraft paper and 3 mil polyethylene extrusion laminate heat-sealed to the aluminum sheet over the entire interface area or a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The poly/kraft protective backing shall be identified on the product to indicate 3 mil polyethylene. The protective backing must qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.
Approved Materials and Vendors Deep-Corrugated Jacketing with 3 Mil Poly/Kraft or 2.5 Mil Poly/Surlyn (a)

Childers Products Co.

Sure-Fit Deep-Corrugated Sheets – Aluminum with 3 Mil

Poly/Kraft or 2.5 Mil Poly/Surlyn

Pabco Div. of Fibreboard Corp.

Deep-Corrugated Aluminum with 3 Mil Poly/Kraft or 2.5 Mil Poly/Surlyn

RPR Products, Inc.

 

CODE 716.7 (Deep-corrugated aluminum jacket, 16 mil acrylic-coated)

 

Material Designation Deep-corrugated aluminum jacket, 16 mil acrylic-coated
Purpose A finish for thermal insulation on vertical vessels. Preferred finish where rigidity, weather or chemical resistance, cleanliness, appearance, oil or solvent spills, or fumes are factors.
Material Description Aluminum sheets with 11/4 in corrugations and a white acrylic coating on the exterior and a protective backing on the interior surface. A more rigid material than Code 716.5.
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: 33 in (36 in available at added cost) Length: Up to 12 ft

Thickness: 0.016 in nominal

Note Exterior surface to have a white acrylic coating nominal 0.8 mil dry-film thickness. Some acids will attack coating. Check exposure before specifying. The protective backing shall be 40 lb/3000 ft2 kraft paper and

3 mil polyethylene extrusion laminate heat-sealed to the aluminum sheet

over the entire interface area or a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The poly/kraft protective backing shall be identified on the product to indicate 3 mil polyethylene. The protective backing must qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.

Approved Materials and Vendors Deep-Corrugated Aluminum Jacket, Acrylic Finish with 3 Mil Poly/Kraft or

2.5 Mil Poly/Surlyn (a)

Childers Products Co.

Sure-Fit Deep-Corrugated Sheets – Aluminum Acrylic-Coated with 3 Mil

Poly/Kraft or 2.5 Mil Poly/Surlyn

Pabco Div. of Fibreboard Corp.

Deep-Corrugated Aluminum with 3 Mil Poly/Kraft or 2.5 Mil Poly/Surlyn

Acrylic-Coated

RPR Products, Inc.

Note:

(a)  State complete specification and required length on order.

CODE 716.8 (Smooth aluminum jacket, 16 mil Tedlar coated)

 

Material Designation Smooth aluminum jacket, 16 mil Tedlar coated
Purpose A finish for thermal insulation where specific chemical resistance, cleanliness, appearance, oil or solvent spills, or fumes are factors
Material Description Smooth aluminum in roll form with a white Tedlar PVF film laminated to the exterior and a protective backing on inner surface(a)
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: Standard 351/2 in

Length: Roll of 100 ft minimum

Thickness of aluminum: 0.016 in nominal

Thickness of Tedlar PVF film: 1.5 mil

Note White Tedlar PVF film 1.5 mil thick laminated to exterior surface resistant to most acids, bases, and solvents. Check exposure before specifying. The protective backing shall be a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The protective backing must qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.
Approved Materials and Vendors Aluminum Jacket, Ultrolon Finish with 2.5 Mil Poly/Surlyn

Childers Products Co.

Aluminum Jacket, Tedlar, Coated with 2.5 Mil Poly/Surlyn

RPR Products, Inc.

Note:

(a)  Additional colors are available on special large orders.

CODE 717.1 (45  and 90  ell covers, two-piece aluminum die-formed)

 

Material Designation 45  and 90  ell covers, two-piece aluminum die-formed
Purpose A finish for thermal insulation on pipe fittings
Material Description Sheet aluminum cold-formed into two-piece covers by die-forming. Ends have 2 in tangents for lap joints with pipe insulation covering. Fits only one combination of pipe size and insulation thickness. Insulation must be mitered per vendor’s pattern to prevent interferences. Inside surface coated with transparent epoxy finish.
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Available for pipe sizes through 12 in and 11/2 diameter or smaller bends

Thickness of formed covers: 0.016 in min

Note Attacked by most acids, chlorides, and some hydroxides. Check exposure before specifying. The protective backing must qualify per SN219P. Humped or ‘universal’ type covers are not acceptable.
Approved Materials and Vendors Ell-Jac, CE5-6 Moisture Barrier(a)

Childers Products Co.

Sure-Fit Elbow Covers

Pabco Div. of Fibreboard Corp.

2-Piece Aluminum Elbow Covers

RPR Products, Inc.

Note:

(a)  Four-piece aluminum die-formed ell covers are available in sizes to 18 in by 2 in.

CODE 717.8 (Aluminum covers for vessel heads)

 

Material Designation Aluminum covers for vessel heads
Purpose Weatherproof and protect insulated heads
Material Description Sheet aluminum cut into gore and beaded, then fabricated into head cover
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Thickness: 0.020 in nominal

Size Range: 1 ft through 20 ft diameter (6 in increments)

Note Attacked by most acids, chlorides, and some hydroxides. Check exposure before specifying. The protective backing shall be a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously

heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The protective backing must qualify per SN219P. Vendor will require specific dimensional information on the vessel. Aluminum sheeting conforms to ASTM B 209.

Approved Materials and Vendors Aluminum Gore Head-Jacs with 2.5 Mil Poly/Surlyn

Childers Products Co.

Aluminum Gore Heat Jacket with 2.5 Mil Poly/Surlyn

Distribution International

Aluminum Gore Head Jacket with 2.5 Mil Poly/Surlyn

RPR Products, Inc.

CODE 717.9 (End cap with pipe collar, two-piece aluminum)

 

Material Designation End cap with pipe collar, two-piece aluminum
Purpose A finish for thermal insulation on open-end pipe insulation
Material Description Sheet aluminum fabricated into two-piece covers by rolling and Pittsburgh lock seal, with a 1 in min wide flange fitted to the outside diameter of the pipe. Fits only one combination of pipe size and insulation thickness.
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Thickness: 0.016 in nominal

Size Range: 4 in by 11/2 in through 24 in by 4 in

Note Attacked by most acids, chlorides, and some hydroxides. Check exposure before specifying. The protective backing shall be a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously

heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The protective backing must qualify per SN219P.

Approved Materials and Vendors Double Flanged Collar-Jac with 2.5 Mil Poly/Surlyn

Childers Products Co.

Double Flanged Collar with 2.5 Mil Poly/Surlyn

RPR Products, Inc.

CODE 720(a) (Glass cloth with adhesive (rewettable))

 

Material Designation Glass cloth with adhesive (rewettable)
Recommended Temperature +343  C max (+650  F max)
Range
Purpose Asbestos-free thermal insulation covering
Material Description A woven glass lagging cloth impregnated with a complete coverage of rewettable, inorganic adhesive
Maximum Leachable Chlorides, see Below 100 ppm
SES N01-F10
Moisture Resistance or Water Water soluble adhesive
Vapor Permeability
Dimensions Width: 40 or 60 in

Length: 50 or 100 yd rolls

Flame-Spread/Smoke-Density 25/50 or less
Rating, See ASTM E 84
Note Must be protected from moisture prior to and after installation.

Self-contained adhesive is instantly activated by dipping in water. Drapes well on compound curved surfaces and around sharp corners. Compatible with most waterproofing mastics and coatings. Not recommended for use on removable-reusable covers that are handled frequently. Lagging adhesive, Code 802.1, or fibrous adhesive, Code 803, is not needed. If used, these materials will attack the glass cloth. See SES N01-F10 for metal substrate protection required.

Approved Materials and Vendors Alpha-Maritex Style No. 84215/9485-RW(b)

Alpha Associates, Inc.

S/2205 RWL Covergard(c)

Southern Mfg., Inc.

Textoglass, Style No. 84217/9995(b), J. P. Stevens Co.
Textoglass, Style No. 2014/9995(d), J. P. Stevens Co.
Claretex Lagging Fabric No. 84205, Diplag Treated(d)

The Claremont Co., Inc.

300-RWL

Newtex Industries

Notes:

(a)  Does not contain respirable fibers.

(b)  15 oz/yd2

(c)  Specify 15 oz/yd2 or 26 oz/yd2 (d)  22 oz/yd2

CODE 723.1 (‘ASJ’ Kraft aluminum laminate – white)

 

Material Designation ‘ASJ’ Kraft aluminum laminate – white
Recommended Temperature +2 to +82  C (+35 to +180  F max)
Range
Purpose An indoor finish for thermal insulation
Material Description Glass mesh, approximately 4 in x 6 in, 0.7 mil aluminum foil and white kraft paper bonded together by a fire-retardant adhesive. Finish creped to minimize wrinkling.
Moisture Resistance or Water Not to exceed 0.02 perms
Vapor Permeability
Dimensions Width: 391/4 in

Other widths on request

Length: 100 yd rolls

Flame-Spread/Smoke-Density 25/50 or less
Rating, See ASTM E 84
Note No soluble salts are to be used as the fire-retardant agent. May be used outdoors if protected with aluminum jacket, Code 716. Laminating adhesive to be insoluble in water and have a softening point of not less than 170  F.
Approved Materials and Vendors Alpha-Temp 10651 ASJ Alpha Associates, Inc.
FB 200 ASJ Compac Corp.

CODE 725 (PVA insulation coating for indoors)

 

Material Designation PVA insulation coating for indoors
Recommended Temperature -46 to 82  C (-50 to +180  F max)
Range
Purpose Indoor fire-resistant protective coating for thermal insulation and an adhesive for canvas jackets
Material Description Brush or spray consistency, white polyvinyl acetate emulsion, suitable for reinforcement with glass cloth
Maximum Leachable Chlorides, see Below 43,000 ppm
SES N01-F10
Moisture Resistance or Water Permeable
Vapor Permeability
Flame-Spread/Smoke-Density 25/50 or less (dry)
Rating, See ASTM E 84
Note Recommended for indoor use only. Should not be applied at temperatures below +40  F. Coverage approx 50 ft2/gal. Store above +32  F.

Drying time: Touch 1 hour through 4 hours. See SES N01-F10

for metal substrate protection required.

Approved Materials and Vendors Foster Sealfas 30-36(a)

H.B. Fuller Co., Foster Products Div.

Chil-Seal CP-50A Childers Products Co.
Eco-Perm Coating 11-02

Mon-Eco Industries, Inc.

Note:

(a)  White, other colors available.

 

CODE 727.1(a) (Flexible braided glass fiber tubing)

 

Material Designation Flexible braided glass fiber tubing
Recommended Temperature +10 to 260  C (+50 to +500  F)
Range
Purpose Thermal insulation for bent pipe or tubing where use of rigid material is impractical
Material Description Lightweight, flexible braided tubing manufactured from continuous filament glass fiber and specially heat-treated
Maximum Leachable Chlorides, see Below 100 ppm
SES N01-F10
Resistance to Handling Breakage Good
Dimensions Fits 1/8 in to 3 in OD tubing
Flame-Spread/Smoke-Density 25/50 or less
Rating, See ASTM E 84
Note Attacked by hydrofluoric and phosphoric acids and concentrated hot alkalies. Unaffected by other corrosive agents. Resists organic solvents. See SES N01-F10 for metal substrate protection required.
Approved Materials and Vendors Thermojacket R Unsaturated

Bentley-Harris Manufacturing Co.

Thermoglass Sleeving, Style No. 10–700, Series 9731 Finish

Amatex Corp.

Alpha Maritex Braided Sleeving, 9400 Series

Alpha Associates, Inc.

Woven Tubing

Auburn Manufacturing Inc.

Note:

(a)  Does not contain respirable fibers.

CODE 728.1 (Tedlar, glass, Hypalon laminate)

CODE 730 (Hypalon coating)

 

Material Designation Hypalon coating
Recommended Temperature -29 to +121  C max (-20 to +250  F max)
Range
Purpose Vapor-barrier finish for thermal insulation in either low temperature service or severely corrosive environment or both
Material Description A pigmented, fire-resistant elastomeric coating. Two-coat system. First coat strikes the surface in webs that bridge porous substrates and produce a smooth water-repellent coating. Top coat seals to produce a vaportight coating. Air spray application only.
Maximum Leachable Chlorides, see Below 100 ppm
SES N01-F10
Moisture Resistance or Water Very low water vapor permeability
Vapor Permeability
Flame-Spread/Smoke-Density 25/50 or less
Rating, See ASTM E 84
Note Excellent resistance to chemicals and some solvents. A primer is recommended on dusty and resilient substrates. Spray only. Compounded with Hypalon synthetic rubber. Drying and recoat time: 4 to 8 hours. See SES N01-F10 for metal substrate protection required.
Approved Materials and Vendors Flexgard Finish System

Guardsman Chemical Coating Corp.

Gacoflex H2500

Gates Engineering Co.

 

CODE 731 (Hypalon mastic)

 

Material Designation Hypalon mastic
Recommended Temperature Range -29 to +121  C max (-20 to +250  F max)
Purpose Chemical-resistant, vapor-barrier finish for thermal insulation, especially irregular surfaces
Material Description Flexible, pigmented, fire-resistant elastomer coating of mastic consistency
Maximum Leachable Chlorides, see Below 100 ppm
SES N01-F10
Moisture Resistance or Water Very low water vapor permeability
Vapor Permeability
Flame-Spread/Smoke-Density 25/50 or less
Rating, See ASTM E 84
Note Contains flammable solvents during application and curing period. May require a primer for adhesion to dusty substrates. Minimum acceptable cured finish: 30 mil applied in at least two coats. Compounded with Hypalon synthetic rubber.

Drying time: Touch 3 hours

Flexibility: 30 mil (6 gal/100 ft2) cured coating can be bent over 1/8 in diameter mandrel through 180 degree arc without cracking per Federal Test Method Standard No. 141. Method 6221. Spray only. Check manufacturer for required spray equipment and technique. See SES N01-F10 for metal substrate protection required.

Approved Materials and Vendors Foster Monolar, Trowel,

60-90 (white)

60-91 (gray) Spray,

60-95 (white)

60-96 (gray) H. B. Fuller Co., Foster Products Div.

 

CODE 734 (Insulation mastic)

 

Material Designation Insulation mastic
Recommended Temperature -18 to +82  C max (0 to +180  F max)
Range
Purpose Protective acrylic mastic coating for thermal insulation
Material Description This code number is for white, other colors are available. Nonasphalt pigmented emulsion mastic for rubber glove, palm, brush, or spray application
Maximum Leachable Chlorides, see Below 150 ppm
SES N01-F10
Flame-Spread/Smoke-Density 25/50 or less
Rating, See ASTM E 84
Note Do not apply at temperature below +40  F Store above +32  F

Drying time: Touch 3 hours

Thorough drying time: 12 to 24 hours

Coverage: 10 to 15 ft2 /gal for the system of tack coat and finish coat using reinforcing.

Do not use as a vapor barrier.

Limited service life for outdoor environment. See SES N01-F10 for metal substrate protection required.

Approved Materials and Vendors Foster Weatherite Mastic

36-10 (Trowel) 46-10 (Spray) H. B. Fuller Co.,

Foster Products Div.

Vi-Cryl CP-10 Trowel, CP-11 Brush

Childers Products Co.

Vimasco WC-5 Mastic

Vimasco Corp.

Eco-Mastic 55-50

Mon-Eco Industries, Inc.

Jaxsan 600

Plastic Coatings Corp.

 

L&L Pro-Tec 638

L&L Coatings Corp.

 

CODE 741 (Vapor-barrier membrane)

 

Material Designation Vapor-barrier membrane
Recommended Temperature -32 to +66  C max (-25 to +150  F max)
Range
Purpose Vapor barrier for thermal insulation
Material Description A flexible membrane consisting of a plastic film coated on one side with adhesive-consistency mastic covered with a release paper
Maximum Leachable Chlorides, see Below 150 ppm
SES N01-F10
Moisture Resistance or Water 0.05 perms max
Vapor Permeability
Dimensions Width: 36 in

Length: 50 or 60 ft rolls with release paper

Flame-Spread/Smoke-Density Rating, See ASTM E 84 Greater than 25/50

Do not use indoors without sprinkler protection or a fireproof finish

Note Protect from heat and direct sunlight prior to use to reduce handling difficulties due to softening. Ambient surface and material temperatures should not be below +40  F at time of application. Overlaps on itself to form a self-sealing seam. Protect from sunlight outdoors and cover as soon as possible after application. Membrane to be 5 to 10 mil plastic film with 40 to

60 mil layer of adhesive-consistency mastic. See SES N01-F10 for metal substrate protection required.

Approved Materials and Vendors Serci Wrap P500

Ultra Industries

Pittwrap SS II

Pittsburgh Corning Corp.

CODE 743(a) (Synthetic organic fiber cloth, open weave)

 

Material Designation Synthetic organic fiber cloth, open weave
Recommended Temperature +121  C max (+250  F max)
Range
Purpose High-elongation reinforcement for mastic finishes over thermal insulation
Material Description An open mesh cloth consisting of mod-acrylic or nylon and polyester fiber and treated with a weave set
Maximum Leachable Chlorides, see Below 150 ppm
SES N01-F10
Flame-Spread/Smoke-Density 25/50 or less
Rating, See ASTM E 84
Note High elongation accommodates thermal and mechanical movement without rupture. Elongation 30%: min 21/2 to 3 oz/yd2: meshes per in from 5 x 5 to 8 x 8 mesh openings per in. Compatible with asphalt cutback and emulsion mastic finishes. May be softened by some solvents such as acetone and ketones. See SES N01-F10 for metal substrate protection required.
Approved Materials and Vendors Elastafab No. 894

Vimasco Corp.

PC Fabric 79

Pittsburgh Corning Corp.

Quality Cloth

Distribution International

Note:

(a)  Does not contain respirable fibers.

CODE 745(a) (High-temperature glass cloth)

 

Material Designation High-temperature glass cloth
Recommended Temperature +343  C max (+650  F max)
Range
Purpose Covering for insulation materials used for removable pads, flange covers, and insulation blankets
Material Description Plain weave fabric, woven with 100% fiberglass high bulk yarns
Maximum Leachable Chlorides, see Below 100 ppm
SES N01-F10
Density 17 oz/yd2
kg/m3 (lb/ft3)
Resistance to Handling Breakage Good
Dimensions Standard Widths (in)

Alpha          38, 50, 60, 72

Amatex       60

Burlington   38, 50, 60

Stevens       38, 50, 60, 72

   
Flame-Spread/Smoke-Density Rating, See ASTM E 84 25/50 or less
Approved Materials and Vendors Alpha-Maritex, Style 2025/9383, Alpha Associates, Inc.

Thermoglass, Style GI9P33, Amatex Corp.

Burlglas, Style 1925, Finish I – 603A, Burlington Industries, Inc.
Textoglass, Style 1925, Finish 9383, J. P. Stevens and Co., Inc.
Claretex 1925, Pad Fabric, The Claremont Co., Inc.
Clark Schwebel Glass Fabric, Style 1925/9383

Clark Schwebel Fiber Glass Corp.

Style 2025 – 100 Finish

Southern Manufacturing, Inc.

AMI-Glass Style GL-2025-9383

Auburn Manufacturing, Inc.

Zetex Style 600

Newtex Industries

Note Maximum service temperature is +1000  F; however, the material retains only approximately 50% of room temperature tensile strength at +700  F and approximately 25% at +900  F. Do not use outdoors or in wet areas. Can be machine sewn. See SES N01-F10 for metal substrate protection required.

Note:

(a)  Does not contain respirable fibers.

CODE 746(a) (High-temperature glass cloth, silicone-coated)

 

Material Designation High-temperature glass cloth, silicone-coated
Recommended Temperature +38 to +260  C max (+100 to +500  F max)
Range
Purpose Covering for insulation materials used for removable-reusable pads, flange covers, and insulation blankets – indoors
Material Description Glass fiber fabric coated with silicone rubber both sides
Maximum Leachable Chlorides, see Below 100 ppm
SES N01-F10
Moisture Resistance or Water Nonporous
Vapor Permeability
Density 15 oz/yd2
kg/m3 (lb/ft3)
Resistance to Handling Breakage Good
Dimensions 36, 38, 48, 50, and 60 in width
Flame-Spread/Smoke-Density 25/50 or less
Rating, See ASTM E 84
Note The maximum service temperature of the silicone rubber coating is +500  F. Water, oil, grease, acid, and alkali resistant. Can be machine-sewn. Do not use outdoors or in wet areas indoors. Available in gray color only. See SES N01-F10 for metal substrate protection required.
Approved Materials and Vendors Alpha-Maritex Style 3201-2-SS Alpha Associates, Inc.
Style 2300 – Silicone-Coated

Southern Manufacturing, Inc.

Lewco 1600S

Lewco Specialty Products, Inc.

Silverjac 1700

Style 3155 Silicone/Glass

McAllister Mills

Textiles Coated, Inc.

Thermoglass, Style G17SIL Amatex Corp.

Note:

(a)  Does not contain respirable fibers.

CODE 746.1(a) (High-temperature glass cloth, silicone-impregnated)

 

Material Designation High-temperature glass cloth, silicone-impregnated
Recommended Temperature +38 to +260  C max (+100 to +500  F max)
Range
Purpose Covering for insulation materials used for removable-reusable pads, flange covers, and insulation blankets – outdoors
Material Description Satin weave glass fiber fabric impregnated with silicone rubber both sides
Maximum Leachable Chlorides, see Below 100 ppm
SES N01-F10
Moisture Resistance or Water Nonporous
Vapor Permeability
Density 17 oz/yd2
kg/m3 (lb/ft3)
Resistance to Handling Breakage Good
Dimensions 36, 38, 48, 50, and 60 in widths
Flame-Spread/Smoke-Density 25/50 or less
Rating, See ASTM E 84
Note The maximum service temperature of the silicone rubber coating is +500  F. Water, oil, grease, acid, and alkali resistant. Can be machine-sewn. Available in gray color only. See SES N01-F10 for metal substrate protection required.
Approved Materials and Vendors Alpha-Maritex Fiber Glass/Silicone Style 3259-2-SS Alpha Associates, Inc.
Silverjac 1700

Textiles Coated, Inc.

Lewco 1700S Lewco 1750SA

Lewco Specialty Products, Inc.

Note:

(a)  Does not contain respirable fibers.

CODE 746.2(a) (High-temperature glass cloth, Teflon-coated)

 

Material Designation High-temperature glass cloth, Teflon-coated
Recommended Temperature +38 to +260  C max (+100 to +500  F max)
Range
Purpose Chemical and weather resistant Teflon-coated cloth developed specifically for fabricating removable-reusable soft insulating covers/pads
Material Description Woven glass fabric coated with Teflon fluorocarbon resins
Maximum Leachable Chlorides, see Below 100 ppm
SES N01-F10
Moisture Resistance or Water Nonporous
Vapor Permeability
Density 14 oz/yd2
kg/m3 (lb/ft3)
Resistance to Handling Breakage Excellent
Dimensions Roll 5 ft wide x 50 yd long
Flame-Spread/Smoke-Density Rating, See ASTM E 84 25/50 or less
 
Note Maximum service temperature of the Teflon coating is +500  F. Water, oil, grease, acid, and alkali resistant. Can be machine-sewn and heat-sealed. Available in gray color only. See SES N01-F10 for metal substrate protection required.
Approved Materials and Vendors Alpha Maritex Style TC-q-14 ‘Teflon’ -Coated Fiberglass

Fabric

Alpha Associates, Inc.

q-Guard 14G Chemfab

Material Technologies Div.

EJ1650

Textiles Coated, Inc.

Note:

(a)  Does not contain respirable fibers.

 

 

CODE 747(a) (High-temperature synthetic cloth)

 

Material Designation High-temperature synthetic cloth
Recommended Temperature Range +288  C max (+550  F max)
Purpose Covering for insulation materials used for removable-reusable insulation indoors
Material Description Heat-resistant, synthetic textile consisting of a combination of glass, Nomex and Kevlar fibers. Also available as tape, roving, braided sleeving, and twisted and braided rope.
Maximum Leachable Chlorides, see SES N01-F10 Below 100 ppm
Density kg/m3 (lb/ft3) 17 and 22 oz/yd2
Resistance to Handling Breakage Excellent
Dimensions 40 and 60 in widths in 50 yd rolls
Flame-Spread/Smoke-Density 25/50 or less
Rating, See ASTM E 84
Note Has high abrasion resistance and high mechanical strength. Other weights of cloth are available. Can be adhered with lagging adhesive Code 802.1 and fibrous adhesive Code 803 and Code 803.2 (trowel grade), and exposed to +550  F without apparent loss of cloth strength. Available only in

pale yellow color. See SES N01-F10 for metal substrate protection required.

Approved Materials and Vendors Nor-Fab 400

Amatex Corp.

Note:

(a)  Does not contain respirable fibers.

CODE 748 (45  and 90  ell covers, one-piece PVC – indoor)

 

Material Designation 45  and 90  ell covers, one-piece PVC – indoor
Recommended Temperature -18 to +66  C max (0 to +150  F max)
Range
Purpose Finish over thermal insulation on pipe fittings. To be used on pipe fittings where fiberglass insulation with factory-applied ASJ (kraft aluminum – white) finish is specified indoors.
Material Description Sheet polyvinylchloride, preformed into one-piece covers. Fits only one combination of fitting size and insulation thickness.
Maximum Leachable Chlorides, see Below 40,000 ppm
SES N01-F10
Moisture Resistance or Water 0.05 perms max
Vapor Permeability
Resistance to Handling Breakage Good
Dimensions Thickness: 0.020 in minimum

Max available size 12 x 11/2 in(a)

Flame-Spread/Smoke-Density 25/50 or less
Rating, See ASTM E 84
Note Covers can be secured with vinyl tape, nylon tacks, or adhesives. Accessories are available from the fitting cover distributors. PVC will soften above 71  C (160  F). Specify one-piece fitting cover – economical fitting cover to be used indoors in low-mechanical abuse areas. Not recommended outdoors. See SES N01-F10 for metal substrate protection required.
Approved Materials and Vendors 300 Series PVC, UVR, Light-Gage Fitting Cover

CEEL-Co

Dura-Jac SX Fitting Cover

Sproule Mfg. Co.

Speedline 2

Great Lakes Inc.

 
LoSmoke

Proto Corp.

P.I.C. FG20

P.I.C. Plastics, Inc.

Zeston 2000

Manville Mechanical Insulation Div. Schuller International, Inc.

 

Note:

(a)  For availability of larger sizes, contact vendor.

CODE 748.1 (45  and 90  ell covers, one-piece PVC)

 

Material Designation 45  and 90  ell covers, one-piece PVC
Recommended Temperature Range -18 to +66  C max (0 to +150  F max)
Purpose Finish over thermal insulation on pipe fittings. To be used on pipe fittings where fiberglass insulation with factory-applied ASJ (kraft aluminum – white) finish is specified indoors.
Material Description Sheet polyvinylchloride, preformed into one-piece covers. Fits only one combination of fitting size and insulation thickness.
Maximum Leachable Chlorides, see SES N01-F10 Below 40,000 ppm
Moisture Resistance or Water Vapor Permeability 0.05 perms max
Resistance to Handling Breakage Good
Dimensions Thickness: 0.030 in minimum

Max available size 20 in OD

Flame-Spread/Smoke-Density Rating, See ASTM E 84 Less than 25/greater than 50. Do not use indoors without sprinkler protection or a fireproof finish.
Note Covers can be secured with vinyl tape, nylon tacks, or adhesives. Accessories are available from the fitting cover distributors. Specify one-piece fitting cover – economical fitting cover to be used indoors in low-mechanical abuse areas. PVC will soften above 71  C (160  F).

Unaffected by ultraviolet rays. Check chemical exposure before specifying. See SES N01-F10 for metal substrate protection required.

Approved Materials and Vendors Ceel-Tite 300 Series Heavy Duty

CEEL-Co.

Dura-Jac SX 0.030 in

Sproule Mfg. Co.

Industrial Weight PVC Proto Corp.
P.I.C. FG30

P.I.C. Plastics, Inc.

Zeston 2000

Heavy Gage

Manville Mechanical Insulation Div. Schuller International, Inc.

 

CODE 748.2 (two-piece PVC flange cover)

 

Material Designation two-piece PVC flange cover
Recommended Temperature Range -18 to +66  C max (0 to +150  F max)
Purpose Corrosion-resistant permanent or removable-reusable flange cover that is suitable for DuPont spacing of pipe insulation at flanges
Material Description Heavy-gauge sheet polyvinylchloride, preformed into two-piece matching covers. Fits only one combination of flange size (150 through 400 lb) and pipe insulation thickness.
Maximum Leachable Chlorides, see SES N01-F10 Below 40,000 ppm
Moisture Resistance or Water Vapor Permeability 0.05 perms max
Resistance to Handling Breakage Good
Dimensions Thickness: 0.040 in minimum

Max available size: 12 in by 21/2 in

Larger sizes available on special order

Flame-Spread/Smoke-Density Less than 25/greater than 50. Do not use indoors without sprinkler protection or a fireproof finish.
Rating, See ASTM E 84
Note Designed to accept 21/2 in thick insulation. The insulation can be installed loose or can be secured to the inside of the cover with adhesive. Can be used indoors or outdoors in moderate mechanical abuse areas. This cover is compatible with white acrylic or Tedlar-coated aluminum pipe insulation jacketing. Unaffected by ultraviolet rays. PVC will soften above 71  C

(160  F). Check chemical exposure before specifying. See SES N01-F10 for metal substrate protection required.

Approved Materials and Vendors EX-L-FLG Proto Corp.

Dura-Jac SX

Flange & Ball Valve Cover

Sproule Mfg. Co.

CODE 748.3 (30 mil PVC jacket)

 

Material Designation 30 mil PVC jacket
Recommended Temperature -18 to +66  C max (0 to +150  F max)
Range
Purpose Finish for thermal insulation where abuse resistance, weather or chemical resistance, cleanliness, appearance, oil or solvent spills, or fumes are factors
Material Description Heavy-gauge polyvinylchloride in roll form
Maximum Leachable Chlorides, see SES N01-F10 Below 40,000 ppm
Moisture Resistance or Water 0.05 perms max
Vapor Permeability
Compressive Strength
Resistance to Handling Breakage Good
Dimensions Width: 351/2 in or 48 in

Length: Roll of 68 ft or 100 ft

Width and length may vary by vendor

Thickness: 0.030 in nominal

Flame-Spread/Smoke-Density Rating, See ASTM E 84 Less than 25/greater than 50. Do not use indoors without sprinkler protection or a fireproof finish.
Note Jacketing can be secured with vinyl tape, nylon tacks, bands, or adhesives. Accessories are available from the jacketing distributors. Jacketing should be limited to 20 in OD applications. To provide proper closure of the jacketing seams upon application, material should be ordered from the vendor precurled or precurling will be required in the field. Can be used indoors and outdoors. Unaffected by ultraviolet rays. PVC will soften above

71  C (160  F). An unsealed slide joint is recommended every 25 ft for thermal expansion of the pipe and jacketing. Provide an unsealed slide joint between fittings when the distance exceeds 8 ft. Check chemical exposure before specifying. See SES N01-F10 for metal substrate protection required.

Approved Materials and Vendors CEEL-Tite 330

CEEL-Co.

Dura-Jac SX 0.030 in

Sproule Mfg. Co.

LoSmoke 30 mil

Proto-Jac

Proto Corp.

P.I.C. FG30

P.I.C. Plastics, Inc.

Zeston 2000 30 mil

Manville Mechanical Insulation Div. Schuller International, Inc.

 

CODE 748.4 (Ribbed panels)

 

Material Designation Ribbed panels
Recommended Temperature

Range

-18 to +66  C max (0 to +150  F max)
Purpose Finish for thermal insulation on vertical vessels. Preferred finish where durability, weather or chemical resistance, cleanliness, appearance, oil or solvent spills, or fumes are factors.
Material Description Heavy-gauge polyvinylchloride in panel form
Maximum Leachable Chlorides, see

SES N01-F10

Below 40,000 ppm
Moisture Resistance or Water

Vapor Permeability

0.05 perms max
Resistance to Handling Breakage Good
Dimensions Thickness: 0.040 in minimum

Panel dimensions upon request from vendor

Flame-Spread/Smoke-Density

Rating, See ASTM E 84

Less than 25/greater than 50. Do not use indoors without sprinkler protection or a fireproof finish.
Note The panels shall be secured with adhesives and bands. Accessories are available from the jacketing distributors. Unaffected by ultraviolet rays. PVC will soften above 71  C (160  F). Check chemical exposure before specifying. Can be used indoors and outdoors. See SES N01-F10 for metal substrate protection required. Additional banding is required for

large-diameter tanks and vessels.

Approved Materials and Vendors Ceel-Co Ribbed Panels

CEEL-Co.

 

CODE 749 (RTP (FRP) jacket)

 

Material Designation RTP (FRP) jacket
Recommended Temperature Range -7 to +149  C max (+20 to +300  F max)
Purpose Corrosion-resistant finish for pipe and equipment with minimum insulation outside diameter of 16 in
Material Description Glass fiber reinforced thermoset plastic resin (RTP)
Maximum Leachable Chlorides, see SES N01-F10 Below 100 ppm
Moisture Resistance or Water Vapor Permeability Good
Resistance to Handling Breakage Good
Dimensions Thickness: 0.030 in nominal Standard width of 48 in 100 ft rolls Other size combinations are available
Flame-Spread/Smoke-Density Rating, See ASTM E 84 Less than 25/greater than 50. Do not use indoors without sprinkler protection or a fireproof finish.
Note Resistant to most acids, bases, and solvents. Check exposure before specifying. Specify that the jacket shall be fabricated with fire- and corrosion-resistant materials. See SES N01-F10 for metal substrate protection required.
Approved Materials and Vendors FRP Jacketing

Pamrod Products Co.

Dura-Jac ‘H.D.’

Sproule Manufacturing Co.

 

CODE 749.1 (RTP (FRP) fitting covers)

 

Material Designation RTP (FRP) fitting covers
Recommended Temperature

Range

-7 to +149  C max (+20 to +300  F max)
Purpose Corrosion-resistant preformed covers for large diameter fittings as an alternate to gore-type metal covers
Material Description Glass-fiber-reinforced thermoset plastic resin (RTP)
Maximum Leachable Chlorides, see

SES N01-F10

Below 100 ppm
Moisture Resistance or Water

Vapor Permeability

Good
Resistance to Handling Breakage Good
Flame-Spread/Smoke-Density

Rating, See ASTM E 84

Less than 25/greater than 50. Do not use indoors without sprinkler protection or a fireproof finish.
Note Resistant to most acids, bases, and solvents. Check exposure before specifying. See SES N01-F10 for metal substrate protection required. Standard colors are aluminum-gray or white.
Approved Materials and Vendors Dur-Jac ‘H.D.’ Flange, Tee, End Cap, 45  and 90  Ell Covers

Sproule Mfg. Co.

FRP Flange, Tee, End Cap, 45  and 90  Ell Covers

Pamrod Products Co.

CODE 750(a) (Metal mesh knitted)

 

Material Designation Metal mesh knitted
Recommended Temperature +649  C max (+1200  F max)
Range
Purpose Abuse-resistant covering for removable-reusable insulation pads – indoors or outdoors. It is also recommended for some insulation pads exposed to temperatures above +650  F.
Material Description A stainless steel wire, knitted into a tubular fabric using a mesh size of 60 density
Resistance to Handling Breakage Excellent
Dimensions Wire Thickness: 0.011 in

Width: 30 in tubular (60 in open width) Length: 132 ft

Note Type 304 stainless steel wire fabric for protecting the outlet surface of removable-reusable insulation pads from severe mechanical abuse or high temperatures. The wire fabric may encapsulate the pad or be limited to the surfaces requiring the protection. The wire fabric is normally secured to the insulation pad with stainless steel hog rings. Some chemicals and chlorides will attack stainless steel. Check exposure before specifying.
Approved Materials and Vendors Alpha-Maritex 91160(a)

Alpha Associated, Inc.

Part No. 55-2350-4480-01

Metal Mesh

Metex Corp.(a)

Note:

(a)  Available crimped for added strength.

CODE 751 (32 mil smooth aluminum jacket)

 

Material Designation 32 mil smooth aluminum jacket
Purpose Finish for thermal insulation where abuse resistance, weather resistance, cleanliness, appearance, oil or solvent spills or fumes, and flame-spread resistance are factors
Material Description Smooth aluminum in roll form with a protective backing on inner surface
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: 36 in or 48 in

Length: Rolls of 100 ft

Thickness of aluminum: 0.032 in nominal

Note Attacked by most acids, chlorides, and some hydroxides. Check exposure before specifying. The protective backing shall be a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously

heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The protective backing must qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.

Approved Materials and Vendors 32 Mil Aluminum Jacket with 2.5 Mil Poly/Surlyn

Childers Products Co.

0.032 in Sure-Fit Roll Jacketing with 2.5 Mil Poly/Surlyn

Pabco Division of Fibreboard Corp.

32 Mil Aluminum Jacket with 2.5 Mil Poly/Surlyn

RPR Products, Inc.

CODE 751.1 (32 mil smooth aluminum jacket, acrylic-coated)

Material Designation 32 mil smooth aluminum jacket, acrylic-coated
Purpose Finish for thermal insulation where abuse resistance, weather or chemical resistance, cleanliness, appearance, oil or solvent spills or fumes, and flame-spread resistance are factors
Material Description Smooth aluminum in roll form with a white acrylic coating on exterior and a protective backing on inner surface
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: 36 in or 48 in

Length: Rolls of 100 ft

Thickness of aluminum: 0.032 in nominal

Note Exterior surface to have a white acrylic coating nominal 0.8 mil dry-film thickness. Some acids will attack coating. Check exposure before specifying. The protective backing shall be a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The

protective backing must qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.

Approved Materials and Vendors 32 Mil Aluminum Jacket with 2.5 Mil Poly/Surlyn

Childers Products Co.

Acrylic Coated Aluminum Jacket, 32 Mil Thick with 2.5 Mil Poly/Surlyn

RPR Products, Inc.

0.032 in Sure-Fit Roll Jacketing, Acrylic-Coated with 2.5 Mil Poly/Surlyn

Pabco Division of Fibreboard Corp.

 

CODE 752 (24 mil smooth aluminum jacket)

Material Designation 24 mil smooth aluminum jacket
Purpose Finish for thermal insulation where abuse resistance, weather resistance, cleanliness, appearance, oil or solvent spills or fumes, and flame-spread resistance are factors
Material Description Smooth aluminum in roll form with a protective backing on inner surface
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: 36 in or 48 in

Length: Rolls of 100 ft

Thickness of aluminum: 0.024 in nominal

Note Attacked by most acids, chlorides, and some hydroxides. Check exposure before specifying. The protective backing shall be a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously

heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The protective backing must qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.

Approved Materials and Vendors 24 Mil Aluminum Jacket with 2.5 Mil Poly/Surlyn

Childers Products Co.

0.024 in Sure-Fit Roll Jacket with 2.5 Mil Poly/Surlyn

Pabco Division of Fibreboard Corp.

24 Mil Aluminum Jacket with 2.5 Mil Poly/Surlyn

RPR Products, Inc.

 

CODE 752.1 (24 mil smooth aluminum jacket, acrylic-coated)

Material Designation 24 mil smooth aluminum jacket, acrylic-coated
Purpose Finish for thermal insulation where abuse resistance, weather or chemical resistance, cleanliness, appearance, oil or solvent spills or fumes, and flame-spread resistance are factors
Material Description Smooth aluminum in roll form with a white acrylic coating on exterior and a protective backing on inner surface
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: 36 in or 48 in

Length: Rolls of 100 ft

Thickness of aluminum: 0.024 in nominal

Note Exterior surface to have a white acrylic coating nominal 0.8 mil dry-film thickness. Some acids will attack coating. Check exposure before specifying. The protective backing shall be a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The

protective backing must qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.

Approved Materials and Vendors 24 Mil Aluminum Jacket, Acrylic Finish with 2.5 Mil Poly/Surlyn

Childers Products Co.

Acrylic Aluminum Jacket, 24 Mil thick with 2.5 Mil Poly/Surlyn

RPR Products, Inc.

0.024 in Sure-Fit Roll Jacketing, Acrylic-Coated with 2.5 Mil Poly/Surlyn

Pabco Division of Fibreboard Corp.

 

CODE 752.2 (24 mil deep-corrugated aluminum jacket)

Material Designation 24 mil deep-corrugated aluminum jacket
Purpose Finish for thermal insulation on vertical vessels. Preferred finish where rigidity, abuse resistance, weather resistance, cleanliness, appearance, oil or solvent spills or fumes, and flame-spread resistance are factors.
Material Description Aluminum sheets with 11/4 in corrugations and a protective backing on the interior surface. A more rigid material than Code 716. Finish: smooth or cross-crimped as specified on order.
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: 33 in or 44 in (36 in available at added costs) Length: 6 ft through 12 ft

Thickness: 0.024 in nominal

Note Attacked by most acids, chlorides, and some hydroxides. Check exposure before specifying. The protective backing shall be 40 lb/3000 ft2 kraft paper and 3 mil polyethylene extrusion laminate heat-sealed to the aluminum sheet over the entire interface area or a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The poly/kraft protective backing shall be identified on the product to indicate 3 mil polyethylene. The protective backing must qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.
Approved Materials and Vendors 24 Mil Deep-Corrugated Aluminum Jacketing with 3 Mil Poly/Kraft or 2.5 Mil

Poly/Surlyn(a)

Childers Products Co.

0.024 in Sure-Fit Deep-Corrugated Sheets – Aluminum with 3 Mil Poly/Kraft or 2.5 Mil Poly/Surlyn

Pabco Division of Fibreboard Corp.

24 Mil Deep-Corrugated Aluminum with 2.5 Mil Poly/Surlyn

RPR Products, Inc.

 

Note:(a)State complete specification and required length on order.

CODE 752.3 (24 mil deep-corrugated aluminum jacket acrylic-coated)

Material Designation 24 mil deep-corrugated aluminum jacket acrylic-coated
Purpose Finish for thermal insulation on vertical vessels. Preferred finish where rigidity, abuse resistance, weather resistance, cleanliness, appearance, oil or solvent spills or fumes, and flame-spread resistance are factors.
Material Description Aluminum sheets with 11/4 in corrugations and a white acrylic coating on the exterior and a protective backing on the interior surface. A more rigid material than Code 716.5.
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: 33 in through 44 in (36 in available at added costs) Length: 6 ft through 12 ft

Thickness: 0.024 in nominal

Note Exterior surface to have a white acrylic coating nominal 0.8 mil dry-film thickness. Some acids will attack coating. Check exposure before specifying. The protective backing shall be 40 lb/3000 ft2 kraft paper and

3 mil polyethylene extrusion laminate heat-sealed to the aluminum sheet

over the entire interface area or a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The poly/kraft protective backing shall be identified on the product to indicate 3 mil polyethylene. The protective backing must qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.

Approved Materials and Vendors 24 Mil Deep-Corrugated Aluminum Jacket, Acrylic Finish with 3 Mil

Poly/Kraft or 2.5 Mil Poly/Surlyn

Childers Products Co.

0.024 in Sure-Fit Deep-Corrugated Sheets – Aluminum, Acrylic-Coated with

3 Mil Poly/Kraft or 2.5 Mil Poly/Surlyn

Pabco Division of Fibreboard Corp.

24 Mil Deep-Corrugated Aluminum with 3 Mil Poly/Kraft or 2.5 Mil

Poly/Surlyn Acrylic-Coated

RPR Products, Inc.

 

Note:

(a)  State complete specification and required length on order.

CODE 752.4 (32 mil deep-corrugated aluminum jacket, Tedlar-coated)

Material Designation 32 mil deep-corrugated aluminum jacket, Tedlar-coated
Purpose Finish for thermal insulation on vertical vessels. A preferred finish where abuse resistance, specific chemical resistance, cleanliness, appearance, oil or solvent spills or fumes, and flame-spread resistance are factors.
Material Description Aluminum sheets with 11/4 in corrugations and a white Tedlar PVF film laminated to the exterior and a protective backing on the interior surface. A more rigid material than Code 752.5.
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: 33 in

Length: Up to 12 ft

Thickness of aluminum: 0.032 in nominal

Thickness of Tedlar PVF film: 1.5 mil

Note White Tedlar PVF film 1.5 mil thick laminated to the exterior surface. Resistant to most acids, bases, and solvents. Check exposure before specifying. The protective backing shall be 40 lb/3000 ft2 kraft paper and

3 mil polyethylene extrusion laminate heat-sealed to the aluminum sheet

over the entire interface area or a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The poly/kraft protective backing shall be identified on the product to indicate 3 mil polyethylene. The protective backing must qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.

Approved Materials and Vendors 32 Mil Deep-Corrugated Aluminum Jacket, Ultrolon Finish with 3 Mil

Poly/Kraft or 2.5 Mil Poly/Surlyn

Childers Products Co.

32 Mil Deep-Corrugated Aluminum Jacket Tedlar Finish with 3 Mil Poly/Kraft or 2.5 Mil Poly/Surlyn

RPR Products Inc.

 

CODE 752.5 (32 mil smooth aluminum jacket, Tedlar-coated)

Material Designation 32 mil smooth aluminum jacket, Tedlar-coated
Purpose Finish for thermal insulation where abuse resistance, specific chemical resistance or weather, cleanliness, appearance, oil or solvent spills or fumes, and flame-spread resistance are factors
Material Description Smooth aluminum in roll form with a white Tedlar PVF film laminated to the exterior and a protective backing on the inner surface
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Good
Dimensions Width: 36 in

Length: Roll of 100 ft

Thickness of aluminum: 0.032 in nominal

Thickness of Tedlar PVF film: 1.5 mil

Note White Tedlar PVF film 1.5 mil thick laminated to the exterior surface. Resistant to most acids, bases, and solvents. Check exposure before specifying. The protective backing shall be a minimum of 2.5 mil total thickness coextruded polyethylene and DuPont Surlyn continuously heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The

protective backing must qualify per SN219P. Aluminum sheeting conforms to ASTM B 209.

Approved Materials and Vendors 32 Mil Aluminum Jacket, Ultrolon Finish with 2.5 Mil Poly/Surlyn

Childers Products Co.

32 Mil Aluminum Jacket, Tedlar coated with 2.5 Mil Poly/Surlyn

RPR Products Inc.

 

CODE 753 (10 mil smooth stainless steel jacket)

Material Designation 10 mil smooth stainless steel jacket
Purpose Finish for thermal insulation where chemical resistance or fire protection (or both) are factors
Material Description Smooth stainless steel in roll form with a protective backing on the inner surface
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Excellent
Dimensions Width: 36 in

Length: Roll of 50 ft min

Thickness: 0.010 in min

Note Type 300 series stainless steel with a 2B mil finish. Low emissivity of bare stainless steel results in surface temperatures up to +40  F greater than other finishes such as mastic or coated metals. For installation, use bands only as indicated in SN215P. Minimum protective backing to be either nominal 40 lb/3000 ft2 kraft paper and 3 mil polyethylene extrusion laminate heat-sealed to the metal over the entire inner surface area or a minimum of

2.5 mil total thickness coextruded polyethylene and DuPont Surlyn

continuously heat-sealed to the metal. The Surlyn shall be a minimum of

1 mil. The poly/kraft protective backing shall be identified on the product to indicate 3 mil polyethylene. The protective backing must qualify per SN219P. Stainless steel sheeting conforms to ASTM A 167 and A 240.

Approved Materials and Vendors 10 Mil Stainless Steel Jacketing/with 3 Mil Poly/Kraft or 2.5 Mil Poly/Surlyn

Barrier

Childers Products Co.

10 Mil Stainless Steel Jacketing/with 3 Mil Poly/Kraft or 2.5 Mil Poly/Surlyn

Barrier

RPR Products, Inc.

0.010 in Sure-Fit Stainless Steel Roll Jacketing, 3 Mil Poly-Weld or 2.5 Mil

Poly/Surlyn Barrier

Pabco Division of Fibreboard Corp.

CODE 753.1 (10 mil stainless steel fitting covers)

Material Designation 10 mil stainless steel fitting covers
Purpose Finish for thermal insulation on pipe fittings where chemical resistance or fire protection (or both) are factors
Material Description Sheet stainless steel cold-formed or rolled into covers. Fits combination of pipe size and insulation thickness
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Excellent
Dimensions Sizes: See manufacturer literature

Thickness: 0.010 in min

Note Type 300 series stainless steel with a 2B mil finish
Approved Materials and Vendors Stainless Steel 90  Univers-Ell Jac, Tee-Jac and End Cap-Jac

Childers Products Co.

Stainless Steel 90  Ell, Tee and End Cap

RPR Products, Inc.

Sure-Fit Stainless Steel 45  and 90  Ells

Pabco Div. of Fibreboard Corp.

CODE 753.4 (10 mil deep-corrugated stainless steel jacket)

Material Designation 10 mil deep-corrugated stainless steel jacket
Purpose Finish for thermal insulation on vertical vessels where chemical resistance or fire protection (or both) are factors
Material Description Stainless steel sheets with 11/4 in corrugations with a protective backing on the inner surface. A more rigid material than Code 753.
Moisture Resistance or Water

Vapor Permeability

Impermeable
Resistance to Handling Breakage Excellent
Dimensions Width: 33 in

Length: Up to 10 ft

Thickness of stainless steel: 0.010 in min

Note Type 300 series stainless steel with a 2B mil finish. Low emissivity of bare stainless steel results in surface temperatures up to +40  F greater than other finishes such as mastic or coated metals. For installation, use bands only as indicated in SN215P. Minimum protective backing to be either nominal 40 lb/3000 ft2 kraft paper and 3 mil polyethylene extrusion laminate heat-sealed to the metal over the entire inner surface area or a minimum of

2.5 mil total thickness coextruded polyethylene and DuPont Surlyn

continuously heat-sealed to the metal. The Surlyn shall be a minimum of 1 mil. The poly/kraft protective backing shall be identified on the product to indicate 3 mil polyethylene. The protective backing must qualify per SN219P. Stainless steel sheeting conforms to ASTM A 167 and A 240.

Approved Materials and Vendors 10 Mil Deep-Corrugated Stainless Steel Jacketing with 3 Mil Poly/Kraft or

2.5 Mil Poly/Surlyn Barrier

Childers Products Co.

10 Mil Deep-Corrugated Stainless Steel Jacketing with 3 Mil Poly/Kraft or

2.5 Mil Poly/Surlyn Barrier

RPR Products, Inc.

0.010 Deep-Corrugated Sure-Fit Stainless Steel Roll Jacketing, 3 Mil

Poly-Weld or 2.5 Mil Poly/Surlyn Barrier

Pabco Division of Fibreboard Corp.