This article is about Fan Coil Installation, checklist and Technical Project Specification as per International Codes and standards.
Fan Coil Installation | Checklist | Technical Project Specification
- Fan Coil Units shall be mounted (unless it is wall mounted) on a concrete housekeeping pad, at a minimum of 100 mm (4″) above the floor or a minimum of 150 mm (6″) above unpaved ground as applicable.
- Fan Coil Units shall be installed at the location indicated on the drawings and in accordance with details of mounting
- Evaporators of Fan Coil units shall be mounted a minimum of 150 mm (6 inch) off the floor, to allow room for condensate trap
- Equipment clearance shall be provided with a minimum of 1 m clearance on each side of equipment with openable panel or controls, unless equipment manufacturer requires greater clearances. Adequate space shall be provided for coil removal
- Vibration isolators shall be provided between Fan Coil Units and foundations to minimize transmitted vibration.
Standards Codes and References For Fan Coil Installation
- SAES-K-001 – Heating, Ventilating and Air Conditioning (HVAC).
- SAES-K-100 – Saudi Aramco Mechanical (HVAC) Code.
- Uniform Mechanical Code (UMC).
- Uniform Fire Code (UFC), 1997.
- HVAC Metal Duct, Hangers and Supports and Insulation Receiving.
- HVAC Chilled Water Piping Lay-out and Support.
- HVAC Condensate Drain Installation | HVAC Engineering.
- HVAC Two Way and Three Way Control Valve Arrangement (Chilled Water Lines).
- HVAC Air Handling Unit (AHU) Installation | HVAC Engineering.
- Air Cooled Condenser Installation | Design | Technical Specification.
- Chilled Water System Components Receiving, Handling, Storage and Preservation Inspection.
- HVAC Exhaust Fan Receiving, Handling and Preservation.
- HVAC Air Handling Unit (AHU) Receiving, Handling, Storage and Preservation..
- HVAC Duct System Handling, Storage and Preservation.
- Commercial Kitchen Hood Installation | Selection | Technical Specification.