1. Scope
This document describes the field preservation at site for Items BXX-C-XXXA/B Adsorbent towers’ internals for Jazan Refinery and Terminal Project.
FIELD PRESERVATION PROCEDURE | ADSORBENT TOWER INTERNAL
2. Receiving Inspection
(1) The surface conditions for wooden packages shall be checked visually.
(2) The quantity of packages shall be checked in accordance with packing list.
(3) The packages shall not be opened during receiving inspection (until installation is ready).
3. Storage instructions
(1) All packages shall be stored in indoors. Indoor is defined as a place of storage
surrounded by floor, roof and wall, which prevents the place from being exposed to
rain, dust, corrosive gas, and direct sunlight, thereby satisfying the purpose of
protecting the packages from breakage, dew condensation and heating, etc.
(2) Packages shall be lifted on the points mentioned on the box.
(3) Before carry in the storage place, dryness of wooden packages shall be checked. If
wet, packages shall be dried by dry air.
(4) The stack of packages is not permitted, and it shall be stored on the floor.
4. Carry out instructions
(1) Packages shall be carried out from storage place just before installation activity.
(2) Before carry out, packages shall be protected by rain cover sheet and it shall be remained until cover open.
(3) Out door storage is not permitted.
(4) Cover plate should be opened in the rain protected roof.
(5) Opening of cover plate is permitted only clear day, and shall not be permitted rainy day.
(6) After opening, the goods shall be immediately moved to work shop with rain protected roof for next activity.