HVAC Grease Filter Installation
- Type I hoods shall be equipped with approved grease filters. UMC Para. 508.5
- Filters shall be placed at the location indicated on the Construction Drawings
- Grease collecting equipment shall be accessible for cleaning. UMC Para. 508.5
- The lowest edge of a grease filter located above the cooking surface shall be at least the height set forth in Table 5-D below. UMC Para. 508.5
Table 5-D Condition Duct system and Hood with
Fire-Extinguishing System (feet)No exposed flame grills, French fryers, etc 2 Exposed-flame and burners 2 Exposed charcoal and charbroil-type fires 31/2 - Filter units shall be installed in frames or holders with handles by which they may be readily removed without the use of tools, unless designed and installed to be cleaned in place. UMC Para. 508.5.1
- Filters shall be removable UMC Para. 508.5.1
- Filters shall be provided with drip intercepting devices. UMC Para. 508.5.1
- Filters shall be installed at an angle greater than 45 degrees from the horizontal. UMC Para. 508.5.2
- Filters shall be equipped with a drip tray beneath the lower edge of the filters. UMC Para. 508.5.2.
Standards Codes and References For HVAC Grease Filter Installation
- Uniform Mechanical Code (UMC)
- Uniform Fire Code (UFC), 1997.
- HVAC Metal Duct, Hangers and Supports and Insulation Receiving.
- HVAC Chilled Water Piping Lay-out and Support.
- HVAC Condensate Drain Installation | HVAC Engineering.
- HVAC Two Way and Three Way Control Valve Arrangement (Chilled Water Lines).
- HVAC Air Handling Unit (AHU) Installation | HVAC Engineering.
- Chilled Water System Components Receiving, Handling, Storage and Preservation Inspection.
- HVAC Exhaust Fan Receiving, Handling and Preservation.
- HVAC Air Handling Unit (AHU) Receiving, Handling, Storage and Preservation..
- HVAC Duct System Handling, Storage and Preservation.