HVAC Two Way and Three Way Control Valve Arrangement (Chilled Water Lines)
- 2-way control valves shall be located on the discharge of each water coil as shown in figure No. 1. See attachment No. 1
- 3-way control valves shall be located on the discharge of each water coil as shown in the figure No. 2. See attachment No. 1.
- Circuit setter or equivalent shall be provided on the discharge side of the water coil, downstream of the control valve, as shown in Figures 1 and 2. See attachment No. 1
- Balancing Valve (Globe valve) shall be provided around 2-way and 3-way control valves, as shown in Figures 1 and 2. See attachment No. 1
- Balancing Valve (Globe Valve) shall be provided on the by-pass piping between the supply piping and the third port of a 3-way control valve, as shown in Figure 2. See attachment No. 1
- By-pass valves shall be located around the Control valves and Flow meters as shown in Figure 1 and 2. See attachment No.1
- Flush valves shall be provided at the following locations:
• On the supply pipe of a water coil after the isolation valve, as shown in Figures 1 and 2. See attached
• On the return pipe of a water coil before the isolation valve, as shown in Figures 1 and 2. See attachment No. 1″ - Isolation valves shall be provided at the following locations:
• On the supply pipe of a water coil up-stream of the flush valve, as shown in Figures 1 and 2. See attachment No. 1
• On the return pipe of a water coil down-stream of the flush valve, as shown in Figures 1 and 2. See attachment No. 1
• On the suction and discharge branch piping of chilled water pumps and suction strainers, without disturbing chilled water system operation. See attachment No. 1″ - Pressure gauges or combination pressure/temperature insertion plugs, such as Pete’s Plug, shall be installed on water coils, at the following locations (See attachment No. 1)
• On the supply pipe, down-stream of the isolation valve, as shown in Figures 1 and 2.
• On the return pipe, up-stream of the isolation valve, as shown in Figures 1 and 2.
• On the suction and discharge branch piping of chilled water pumps.” - Thermometer wells or combination pressure/temperature insertion plugs, shall be installed at the following locations:
• On the supply pipe of a water coil down-stream of the isolation valve, as shown in Figures 1 and 2. See attachment No. 1
• On the return pipe of a water coil up-stream of the isolation valve, as shown in Figures 1 and 2. See attachment No. 1″
Strainers shall be provided at locations shown in Figures 1 and 2. See attachment No. 1.
Standards Codes and References For HVAC Two Way and Three Way Control Valve Arrangement (Chilled Water Lines)
- SAES-K-001 — Heating, Ventilating and Air Conditioning (HVAC).
- HVAC Metal Duct, Hangers and Supports and Insulation Receiving
- HVAC Chilled Water Piping Lay-out and Support
- HVAC Condensate Drain Installation | HVAC Engineering