Skip to content

TRANSMITTER POWER SUPPLY CABLES

‘G’ for ground (earth) indicates that one of the conductors has a green and yellow coloured
insulation. E.g.: 3G1.5 which indicates a cable with 3 x 1.5 mm² conductors (one of which
is a yellow/green conductor)

Cable U1000 R2V

TRANSMITTER POWER SUPPLY CABLES
Conventional cable U1000 R2V

These cables are designed for normal use in industry and are particularly recommended in
fixed low voltage energy distribution installations. Multi-conductor cables are well-adapted
to remote command and control installations. When there is a risk of chemical attack
(corrosion) or prolonged immersion, use 1000 RGPFV. When there is a high ambient
temperature, apply the correction factor.

Installation

These cables can be used in cable trays, channels and troughs or fixed to the walls. They
can be buried if they have additional mechanical protection.

Minimum bend radius

For fixed installation: 6 times the external diameter. During installation, this value must be
doubled.

Identification of conductors

2 conductors: blue + brown

3 conductors = Y / G + blue + brown or brown + black + grey

Electrical characteristics

TRANSMITTER POWER SUPPLY CABLES
Table: Electrical characteristics of cable U1000 R2V

Flexible core cable HO7RN-F

TRANSMITTER POWER SUPPLY CABLES
Cable HO7 RN-F

This cable is particularly well adapted as a power supply cable for mobile site equipment,
electric tools and construction worksites. It can be used up to 0.6/1KV for protected fixed
installations and as power supply cable for motors for lift equipment and similar equipment.

Installation

Cable designed to operate out of doors. When it is buried, provide a mechanical protection
(trough, conduit, etc.).

Bend radius

In use: 6 to 8 times the external diameter of the cable. In static use: 3 times the external
diameter.

Identification of conductors

  • 1 conductor = black
  • 2 conductors = blue + brown
  • 3 conductors = Y/G + blue + brown

Electrical characteristics

TRANSMITTER POWER SUPPLY CABLES
Electrical characteristics of cable HO7 RN-F

Leave a Reply

Your email address will not be published. Required fields are marked *